Basic Accuracy: Experience unparalleled precision with a basic accuracy of ±0.04%, reaching a remarkable maximum of ±0.025% for the most exacting applications.
Range Ratio: Benefit from an impressive range ratio of 100:1, offering unparalleled flexibility to meet diverse pressure measurement needs.
Response Time: Swift response within 90ms ensures rapid and accurate data refresh every 50ms, enhancing operational efficiency.
Range Range: Differential Pressure: Effortlessly measure differential pressures from 0-100 Pa up to an astounding 14MPa.
Pressure Range: Seamlessly handle pressures ranging from 0-1 kPa to a formidable 70MPa, accommodating a wide array of industrial requirements.
Output Signal: Transmit data reliably using a 4-20 mA signal superimposed with HART protocol communication, compatible with both HART 6.0 and HART 7.0 versions.
PROFIBUS-PA Fieldbus Communication: Integrate effortlessly with version 3.02, ensuring robust and consistent communication across systems.
FF Fidbus Communication: Utilize Version 6.1.1 for seamless connectivity, optimizing operations with modern fieldbus technology.
Overload Limit: Differential Pressure: Withstand extreme conditions with a differential pressure overload limit of 42MPa, ensuring durability and resilience.
Pressure Overload: Handle impressive pressure overloads of up to 105MPa, ideal for demanding industrial environments.
Effect of Static Pressure: Maintain accuracy with a minimal effect of 0.03%FS per 16MPa static pressure, ensuring reliable measurements.
Temperature Range: Ambient Temperature: Operate confidently in ambient temperatures from -40ºC to 80ºC. For specific explosion-proof requirements, consult the grade.
Process Temperature: Tackle diverse processes with a temperature range from -90ºC to an intense 700ºC, suitable for extreme applications.
LCD Temperature: Ensure clear visibility and performance in temperatures ranging from -35ºC to 80ºC.
Long-term Drift: Achieve stable performance over time with a long-term drift of only ±0.1%FS over a decade, affirming the reliability of your operations.
Temperature Effect: Guarantee measurement accuracy with a temperature effect of (0.06 * r + 0.01)% per 28ºC, adaptable within a range of -40ºC to 80ºC.
Explosion-proof Grade: NEPSI: Type Ex iaIICT4 Ga, suitable for ambient temperatures from -40ºC to 60ºC, ensuring safety in hazardous environments.
NEPSI: Intrinsic Safety: Type Ex iaIICT6 Ga for ambient temperatures -40ºC to 40ºC, providing secure operation in potentially explosive conditions.
NEPSI: Explosive Type: Ex dIICT6 Gb, compatible with ambient temperatures -40ºC to 60ºC, safeguarding against explosive threats.
NEPSI: Dust Explosion: Protection with Ex tD A21 IP67 T85ºC certification, ensuring robustness against dust-induced explosions.
NEPSI: 'n' Explosion-proof: Certified Ex nACT6 Gc for ambient temperatures -40ºC to +60ºC, enhancing safety in variable conditions.
ATEX Certification: Ben Ex II 1 G Ex iaIICT4 Ga, affirming compliance with stringent international safety standards.
ATEX: Burst Certification: Ex II 1 / 2 G Ex dbIICT6-T 4 Ga / Gb, ensuring top-tier safety against burst hazards.
IECEx: Intrinsic Safety: Certified Ex iaIICT4 Ga, offering reliable protection in explosive environments.
IECEx: Burst: Certified Ex dbIICT6-T 4 Ga / Gb, ensuring safety in high-risk burst scenarios.