Basic accuracy: Achieve remarkable precision with a basic accuracy of ±0.04%, with an outstanding maximum accuracy of ±0.025%.
Range ratio: The sensor boasts an impressive range ratio of 100:1, making it versatile for diverse applications.
Response time: Experience rapid responsiveness with a swift response time of just 90ms, complemented by a fast data refresh rate of 50ms.
Range range: With a differential pressure range from 0-100 Pa up to 14MPa, this sensor adapts to a wide spectrum of pressures.
Pressure range: Capable of handling pressures from 0-1 kPa up to a formidable 70MPa, ensuring robustness in measurement.
Output signal: The sensor communicates seamlessly with a 4-20 mA output signal, enhanced by HART protocol communication (version HART6.0/ HART 7.0).
PROFIBUS-PA fieldbus communication: Integrated with version 3.02, ensuring reliable and efficient data exchange.
FF Fidbus Communication: Equipped with the advanced Version 6.1.1 for superior field communication capabilities.
Overload limit: Designed to withstand high pressures, the differential pressure overload limit extends to a substantial 42MPa.
Pressure overload capacity: Strengthened with the ability to endure pressures up to an imposing 105MPa.
Effect of static pressure: Minimal impact with only 0.03%FS effect at a static pressure of 16MPa, ensuring consistent performance.
Temperature range: Operates efficiently in ambient temperatures from -40ºC to 80ºC, with specific parameters for explosion-proof ranges.
Process temperature: Can handle extreme process temperatures between -90ºC and 700ºC, offering flexibility for various industrial applications.
LCD temperature: The LCD functions optimally between -35ºC and 80ºC, maintaining display clarity and reliability.
Long-term drift: Boasts an impressive long-term stability with a drift of just ± 0.1%FS over a decade.
Temperature Effect: Exhibits a minimal temperature effect of (0.06 * r + 0.01)% over the range of -40ºC to 80ºC, ensuring accuracy.
Explosion-proof grade: Certified by NEPSI for Type Ex iaIICT4 Ga, suitable for ambient temperatures from -40ºC to 60ºC.
NEPSI: Intrinsic safety Ex iaIICT6 Ga, ideal for ambient ranges from -40ºC to 40ºC.
NEPSI: Explosive type Ex dIICT6 Gb, functional within ambient temperatures of -40ºC to 60ºC.
NEPSI: Dust explosion protection with Ex tD A21 IP67 T85ºC, ensuring safety in dusty environments.
NEPSI: 'n' explosion-proof certification Ex nACT6 Gc, operable between -40ºC and +60ºC.
ATEX: Certified for Ben Ex II 1 G Ex iaIICT4 Ga, enhancing safety in explosive atmospheres.
ATEX: Burst protection with Ex II 1 / 2 G Ex dbIICT6-T 4 Ga / Gb, providing reliable safety measures.
IECEx: Intrinsic safety accredited with Ex iaIICT4 Ga, ensuring safe operations in hazardous conditions.
IECEx: Burst protection certified with Ex dbIICT6-T 4 Ga / Gb, offering dependable safety in explosive environments.